PAGE 2 10 NOV 2006 MAN0315-07
DIQ722
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
2 WIRING
2.1 Input / Output Connector Wiring
Warning: To protect the module and associated wiring from load faults, use external (
10 A)
fuse(s) as shown. This warning affects DIQ722, Revisions C or higher.
Warning: Connecting high voltage to any I/O pin may cause high voltage to appear at other I/O
pins.
Warning: Wiring the line side of the AC source to loads connected to outputs 1 through 10 and
the neutral side of the AC source to the output common(s) would create a Negative Logic
condition, which may be considered an unsafe practice.
*
OCS Bottom View
Shows
Corresponding I/O Pin
Signal Pin
DIQ722
I1 Input 1
I2 Input 2
I3 Input 3
I4 Input 4
C1 Common for Inputs
1,2,3,4
Q1 Output 1
Q2 Output 2
Q3 Output 3
Q4 Output 4
Q5 Output 5
C2 Common for Outputs
1,2,3,4,5
Q6 Output 6
Q7 Output 7
Q8 Output 8
Q9 Output 9
Q10 Output 10
C3 Common for Outputs
6,7,8,9,10
VC Relay Coil power common,
connected to bus common
internally.
V+ Relay Coil power + 18 to
+30VDC, 90mA max.
*
LOAD
I1
I2
I3
I4
Q3
C2
V+
Q5
C3
VC
Q1
Q2
C1
Q4
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
Q9
Q8
Q7
Q6
Q10
C3
Q9
Q10
120VAC
L
N
18-30VDC
001DIQ013-R1
5-250VAC
OR
5-30VDC
N
L
5-250VAC
OR
5-30VDC
N
L