MAN0953-02-EN Specifications / Installation
1/6/2011 Page 2 of 4
2.1 I/O Jumper Settings
3 Digital Input Wiring Details
5 Analog I/O Wiring Details
4 Digital Output Wiring Details
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XLe can be wired for Positive Logic inputs or
Negative Logic inputs.
The chart above demonstrates the effect of digital filtering on an analog
input value. The Digital Filtering level is set in Cscape as part of the I/O
Configuration.
Analog Input Digital Filtering
Analog In Settings
AI1 AI2
JP4
ANALOG OUTPUT SETTING
VOLTAGE OR CURRENT
Note: When using JP4 (output) or
JP2 / JP3 (inputs), each channel can
be independently configured. For
example, JP2 can be configured for
10 V and JP3 can be configured as an
RTD.
J1 Orange
Positive Logic
Digital In
J2 Black
Positive Logic
Digital Outputs
J2 Black
Positive Logic
Digital Outputs
0 -10 V Analog Out
AQ1
0V
10VDC
4 - 20 mA Analog Out
AQ1
0V
20mA
Thermocouple In
T1+
T1-
0 – 10 V Analog In
0-10VDC
MA1
V1
0V
NC
RTD In
T1+
T1-
0V
Note: Be sure to wire 0 V
to V1 as shown for proper
operation.
* IMPORTANT: the two analog
outputs are referenced at
registers %AQ9 & %AQ10 in
the application program
Note:
Loop Power requirements are determined by the
transmitter specification.